数字量输出模块 SIPLUS SM 1222 信号模块
Overview
●为 CPU 的集成 I/O 提供更多的数字量输出
●灵活地选择控制器以满足相应任务需要
●用于使用附加输出对系统进行后续扩展
●+60 ℃ 到 +70 ℃,最多可同时控制输入的 50%
注意:
SIPLUS extreme 产品是基于西门子工业标准产品的。此处列出的内容来自相关的标准产品。添加了特定 SIPLUS extreme 信息
Area of application
数字量输出模块允许将数字信号从控制器输出到过程。
这为用户提供了下列优势:
●最佳适应性:
使用可以根据需要混合的信号模块,用户可以使其控制器准确地满足相关任务的要求。这可以避免产生不必要的投资。可以使用带有 8 个、16 个和 32 个输入/输出通道的模块。
●灵活性:
如果任务后续有所扩展,可以升级控制器。更新用户程序非常简单。
Functions
SM 1222 数字量输出信号模块将 SIMATIC S7-1200 的内部信号电平转换为过程所需的外部信号电平。
Technical Specifications
Order number | 6AG1222-1BF32-2XB0 | 6AG1222-1BF32-4XB0 | 6AG1222-1BH32-2XB0 | 6AG1222-1BH32-4XB0 |
---|---|---|---|---|
SIPLUS S7-1200 SM 1222 8DQ | SIPLUS S7-1200 SM 1222 8DQ | SIPLUS S7-1200 SM 1222 16DQ | SIPLUS S7-1200 SM 1222 16DQ | |
Product type designation | ||||
Input current | ||||
from backplane bus 5 V DC, max. | 120 mA | 120 mA | 140 mA | 140 mA |
Power loss | ||||
Power loss, typ. | 1.5 W | 1.5 W | 2.5 W | 2.5 W |
Digital outputs | ||||
Number of digital outputs | 8 | 8 | 16 | 16 |
| 1 | 1 | 1 | 1 |
short-circuit protection | No; to be provided externally | No; to be provided externally | No; to be provided externally | No; to be provided externally |
Switching capacity of the outputs | ||||
| 0.5 A | 0.5 A | 0.5 A | 0.5 A |
| 5 W | 5 W | 5 W | 5 W |
Output voltage | ||||
| 24 V | 24 V | 24 V | 24 V |
| 0.1 V; with 10 kOhm load | 0.1 V; with 10 kOhm load | 0.1 V; with 10 kOhm load | 0.1 V; with 10 kOhm load |
Output current | ||||
| 0.5 A | 0.5 A | 0.5 A | 0.5 A |
| 10 µA | 10 µA | 10 µA | 10 µA |
Output delay with resistive load | ||||
| 50 µs | 50 µs | 50 µs | 50 µs |
| 200 µs | 200 µs | 200 µs | 200 µs |
Total current of the outputs (per group) | ||||
horizontal installation | ||||
| 4 A; Current per mass | 4 A; Current per mass | 8 A; Current per mass | 8 A; Current per mass |
Relay outputs | ||||
Switching capacity of contacts | ||||
| 0.5 A | 0.5 A | 0.5 A | 0.5 A |
| 5 W | 5 W | 5 W | 5 W |
| 0.5 A | 0.5 A | 0.5 A | 0.5 A |
Cable length | ||||
| 500 m | 500 m | 500 m | 500 m |
| 150 m | 150 m | 150 m | 150 m |
Interrupts/diagnostics/status information | ||||
Alarms | ||||
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Diagnostic messages | ||||
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Diagnostics indication LED | ||||
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Potential separation digital outputs | ||||
| 1 | 1 | 1 | 1 |
| 500 V AC | 500 V AC | 500 V AC | 500 V AC |
Degree and class of protection | ||||
Degree of protection acc. to EN 60529 | ||||
| Yes | Yes | Yes | Yes |
Standards, approvals, certificates | ||||
CE mark | Yes | Yes | Yes | Yes |
Ambient conditions | ||||
Free fall | ||||
| 0.3 m; five times, in dispatch package | 0.3 m; five times, in dispatch package | 0.3 m; five times, in dispatch package | 0.3 m; five times, in dispatch package |
Ambient temperature during operation | ||||
| -40 °C; = Tmin; startup @ -25 °C | -20 °C; = Tmin; startup @ 0 °C | -40 °C; = Tmin; startup @ -25 °C | -20 °C; = Tmin; startup @ 0 °C |
| 70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4 (no adjacent points) for horizontal mounting position | 60 °C; = Tmax | 70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 8 (no adjacent points) for horizontal mounting position | 60 °C; = Tmax |
Ambient temperature during storage/transportation | ||||
| -40 °C | -40 °C | -40 °C | -40 °C |
| 70 °C | 70 °C | 70 °C | 70 °C |
Extended ambient conditions | ||||
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | ||||
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | ||||
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | ||||
required front connector | Yes | Yes | Yes | Yes |
Mechanics/material | ||||
Type of housing (front) | ||||
| Yes | Yes | Yes | Yes |
Dimensions | ||||
Width | 45 mm | 45 mm | 45 mm | 45 mm |
Height | 100 mm | 100 mm | 100 mm | 100 mm |
Depth | 75 mm | 75 mm | 75 mm | 75 mm |
Weights | ||||
Weight, approx. | 180 g | 180 g | 220 g | 220 g |
Order number | 6AG1222-1HF32-2XB0 | 6AG1222-1HF32-4XB0 | 6AG1222-1HH32-2XB0 | 6AG1222-1HH32-4XB0 |
---|---|---|---|---|
SIPLUS S7-1200 SM 1222 8DQ RLY | SIPLUS S7-1200 SM 1222 8DQ RLY | SIPLUS S7-1200 SM 1222 16DQ RLY | SIPLUS S7-1200 SM 1222 16DQ RLY | |
Product type designation | ||||
Supply voltage | ||||
permissible range, lower limit (DC) | 20.4 V | 20.4 V | ||
permissible range, upper limit (DC) | 28.8 V | 28.8 V | ||
Input current | ||||
from backplane bus 5 V DC, max. | 120 mA | 120 mA | 135 mA | 135 mA |
Power loss | ||||
Power loss, typ. | 4.5 W | 4.5 W | 8.5 W | 8.5 W |
Digital inputs | ||||
Number of digital inputs | 0 | 0 | ||
Digital outputs | ||||
Number of digital outputs | 8 | 8 | 16 | 16 |
| 2 | 2 | 1 | 1 |
short-circuit protection | No; to be provided externally | No; to be provided externally | No; to be provided externally | No; to be provided externally |
Switching capacity of the outputs | ||||
| 2 A | 2 A | 2 A | 2 A |
| 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC |
Output voltage | ||||
| 5 V DC to 30 V DC | 5 V DC to 30 V DC | 5 V DC to 30 V DC | 5 V DC to 30 V DC |
| 5 V AC to 250 V AC | 5 V AC to 250 V AC | 5 V AC to 250 V AC | 5 V AC to 250 V AC |
Output current | ||||
| 2 A | 2 A | 2 A | 2 A |
Output delay with resistive load | ||||
| 10 ms | 10 ms | 10 ms | 10 ms |
| 10 ms | 10 ms | 10 ms | 10 ms |
Total current of the outputs (per group) | ||||
horizontal installation | ||||
| 10 A; Current per mass | 10 A; Current per mass | 10 A; Current per mass | 10 A; Current per mass |
Relay outputs | ||||
| 8 | 8 | 16 | 16 |
| 24 V | 24 V | 24 V | 24 V |
| mechanically 10 million, at rated load voltage 100,000 | mechanically 10 million, at rated load voltage 100,000 | mechanically 10 million, at rated load voltage 100,000 | mechanically 10 million, at rated load voltage 100,000 |
Switching capacity of contacts | ||||
| 2 A | 2 A | 2 A | 2 A |
| 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC |
| 2 A | 2 A | 2 A | 2 A |
Cable length | ||||
| 500 m | 500 m | 500 m | 500 m |
| 150 m | 150 m | 150 m | 150 m |
Interrupts/diagnostics/status information | ||||
Alarms | ||||
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Diagnostic messages | ||||
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Diagnostics indication LED | ||||
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Potential separation digital outputs | ||||
| Relay, dry contact | Relay, dry contact | Relays | Relay, dry contact |
| 2 | 2 | 4 | 4 |
| 1500 V AC for 1 minute | 1500 V AC for 1 minute | 1500 V AC for 1 minute | 1500 V AC for 1 minute |
Permissible potential difference | ||||
between different circuits | 750 V AC for 1 minute | 750 V AC for 1 minute | 750 V AC for 1 minute | 750 V AC for 1 minute |
Degree and class of protection | ||||
Degree of protection acc. to EN 60529 | ||||
| Yes | Yes | Yes | Yes |
Standards, approvals, certificates | ||||
CE mark | Yes | Yes | Yes | Yes |
Ambient conditions | ||||
Free fall | ||||
| 0.3 m; five times, in dispatch package | 0.3 m; five times, in dispatch package | 0.3 m; five times, in dispatch package | 0.3 m; five times, in dispatch package |
Ambient temperature during operation | ||||
| -40 °C; = Tmin; startup @ -25 °C | -20 °C; = Tmin; startup @ 0 °C | -40 °C; = Tmin; startup @ -25 °C | -20 °C; = Tmin; startup @ 0 °C |
| 70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4 (no adjacent points) for horizontal mounting position | 60 °C; = Tmax | 70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 8 (no adjacent points) for horizontal mounting position | 60 °C; = Tmax |
| 5°C to 55°C, 3°C / minute | |||
Ambient temperature during storage/transportation | ||||
| -40 °C | -40 °C | -40 °C | -40 °C |
| 70 °C | 70 °C | 70 °C | 70 °C |
Extended ambient conditions | ||||
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
| -25 °C | |||
Relative humidity | ||||
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | ||||
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | ||||
required front connector | Yes | Yes | Yes | Yes |
Mechanics/material | ||||
Type of housing (front) | ||||
| Yes | Yes | Yes | Yes |
Dimensions | ||||
Width | 45 mm | 45 mm | 45 mm | 45 mm |
Height | 100 mm | 100 mm | 100 mm | 100 mm |
Depth | 75 mm | 75 mm | 75 mm | 75 mm |
Weights | ||||
Weight, approx. | 190 g | 190 g | 260 g | 260 g |