可编程控制器S7-1200
联系方式
江苏震旦电气科技有限公司
地址:江苏省常州市天宁区龙城大道150号1号楼
总机:0519-86679200 86679300 86679500 86679600 86679700
E-mail:cherry@zhendanele.com

SIPLUS SB 1223 信号板

发布日期:2017-12-26 14:54:33  浏览量:

2015917164811661.jpg

Overview

●数字量输入和输出作为 SIPLUS S7-1200-CPU 的集成 I/O 的补充

●可直接插入 CPU (不可用于 +70 °C 版本中)


注意:

SIPLUS extreme 产品是基于西门子工业标准产品的。此处列出的内容来自相关的标准产品。添加了特定 SIPLUS extreme 信息

icon_up_arrow.png

Area of application

SB 1223 数字量输入/输出信号模块允许:

●将控制器与过程中的数字信号连接

●将数字信号从控制器输出到过程。

icon_up_arrow.png

Design

信号板直接插到每个 S7-1200 CPU 前面的插座中。

●安装:

信号板直接插到 SIMATIC S7-1200 CPU 中,因此可以电气、机械地连接到 CPU

●CPU 的安装尺寸保持不变

●由于所有信号板均配备可拆卸的连接端子(“独立接线”),所以更换方便。

icon_up_arrow.png

Functions

SB 1223 数字量输入/输出信号板

●将过程中的外部数字信号电平转换为 S7-1200 的内部信号电平,

●还可将 S7-1200 的内部信号电平转换为过程所需的外部信号电平

icon_up_arrow.png

Technical Specifications

●min.

Order number6AG1223-0BD30-4XB06AG1223-0BD30-5XB06AG1223-3AD30-5XB06AG1223-3BD30-5XB0

SIPLUS S7-1200 SB1223 2DI / 2DOSIPLUS S7-1200 SB1223 2DI/2DOSIPLUS S7-1200 SB1223 2DI/2DQ, 5VDCSIPLUS S7-1200 SB1223 2DI/2DQ, 24VDC
Product type designation



Supply voltage



permissible range, lower limit (DC)20.4 V20.4 V

permissible range, upper limit (DC)30 V30 V

Input current



from backplane bus 5 V DC, typ.50 mA50 mA50 mA50 mA
Output voltage



Power supply to the transmitters



  • ●Supply current, max.

4 mA; per channel4 mA; per channel4 mA; per channel4 mA; per channel
Power loss



Power loss, typ.<1 W            1 W1 W1 W
Digital inputs



Number of digital inputs2; Current-sinking2; Current-sinking2; Current-sourcing2; Current-sourcing
  • ●in groups of

1111
Input characteristic curve in accordance with IEC 61131, type 1YesYesYesYes
Number of simultaneously controllable inputs



all mounting positions



  • — up to 40 °C, max.

2222
Input voltage



  • ●Type of input voltage

DCDC

  • ●Rated &#118alue (DC)

24 V24 V5 V24 V
  • ●for signal "0"

0 to 5 V0 to 5 V0 to 1 V0 to 5 V
  • ●for signal "1"

+15 to +30V+15 to +30V2 to 6 V+15 to +30V
Input current



  • ●for signal "0", max. (permissible quiescent current)

1 mA1 mA3 mA2 mA
  • ●for signal "1", min.



6 mA5.8 mA
  • ●for signal "1", typ

0.5 A0.5 A
14 mA
Input delay (for rated &#118alue of input voltage)



for standard inputs



  • — Parameterizable

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of fourYes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of fourYes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of fourYes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
  • — at "0" to "1", max.

2 µs2 µs2 µs2.5 µs
  • — at "1" to "0", max.

10 µs10 µs

for interrupt inputs



  • — Parameterizable

YesYesYesYes
for counter/technological functions



  • — Parameterizable

YesYesYesYes
Cable length



  • ●shielded, max.

500 m500 m50 mStandard input: 500 m, high-speed counters: 50 m
  • ●unshielded, max.

300 m300 m

Digital outputs



Number of digital outputs2; MOSFET, solid-state (current-sinking/current-sourcing)2; MOSFET, solid-state (current-sinking/current-sourcing)2; MOSFET, solid-state (current-sinking/current-sourcing)2; MOSFET, solid-state (current-sinking/current-sourcing)
  • ●in groups of

1111
short-circuit protectionNoNoNoNo
Switching capacity of the outputs



  • ●with resistive load, max.

0.5 A0.5 A0.1 A0.1 A
  • ●on lamp load, max.

5 W5 W

Load resistance range



  • ●upper limit

0.6 &#8486;0.6 &#8486;5 &#8486;10 &#8486;
Output voltage



  • ●Rated &#118alue (DC)

24 V24 V5 V24 V
  • ●or signal "0", max.

0.1 V; with 10 kOhm load0.1 V; with 10 kOhm load0.4 V0.1 V; with 10 kOhm load
  • ●for signal "1", max.



6 V
Output current



  • ●for signal "1" rated &#118alue

0.5 A0.5 A0.1 A0.1 A
  • ●for signal "1" permissible range, max.



0.11 A
  • ●for signal "0" residual current, max.

10 µA10 µA
10 µA
Cable length



  • ●shielded, max.

<500 m            500 m50 m50 m
  • ●unshielded, max.

150 m150 m

Interrupts/diagnostics/status information



Alarms



  • ● Alarms

YesYesYesYes
Diagnostic messages



  • ●Diagnostic functions

YesYesYesYes
Diagnostics indication LED



  • ●for status of the inputs

YesYesYesYes
  • ●for status of the outputs

YesYesYesYes
Degree and class of protection



Degree of protection acc. to EN 60529



  • ●IP20

YesYesYesYes
Standards, approvals, certificates



CE markYesYes

Ambient conditions



Free fall



  • ●Fall height, max.

0.3 m; five times, in dispatch package0.3 m; five times, in dispatch package0.3 m; five times, in dispatch package0.3 m; five times, in dispatch package<
Ambient temperature during operation



0 °C; = Tmin-25 °C; = Tmin-25 °C; = Tmin-25 °C; = Tmin
  • ●max.

55 °C; = Tmax55 °C; = Tmax55 °C; = Tmax55 °C; = Tmax
Ambient temperature during storage/transportation



  • ●min.

-40 °C-40 °C-40 °C-40 °C
  • ●max.

70 °C70 °C70 °C70 °C
Extended ambient conditions



  • ●relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity



  • — With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)100 %; RH incl. condensation/frost (no commissioning under condensation conditions)100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance



  • — against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
  • — against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
  • — against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Mechanics/material



Type of housing (front



  • ● plastic

YesYesYesYes
Dimensions



Width38 mm38 mm38 mm38 mm
Height62 mm62 mm

62 mm

62 mm
Depth21 mm21 mm21 mm21 mm
Weights



Weight, approx.40 g40 g40 g40 g

详细产品信息请访问:https://mall.industry.siemens.com/mall/zh/cn/Catalog/Products/10049381?tree=CatalogTree


    联系我们

  • 联系方式
  • 总机:0519-86679200 86679300 86679500 86679600 86679700
  • 传真:0519-89991206
  • 地址:江苏省常州市天宁区龙城大道150号1号楼
  • 邮编:213021
  • E-mail:cherry@zhendanele.com
  • 官方微信公众平台